UltraDb
Log in Get started
<- Reference

Circuit Breakers and Switchers

Medium-Voltage Air Circuit Breaker Acceptance Test

What it is

A medium-voltage air circuit breaker acceptance test is a field protocol that proves an air-break breaker will carry load, interrupt fault current, and respond to its protection before it is put in service. It records the breaker's identification (manufacturer, model and catalog number, serial number, rated voltage, rated continuous current, interrupting rating, basic impulse level, rated control voltage, mechanism type, and equipment designation) with the as-found and as-left operation counter readings, then runs a nineteen-item visual and mechanical inspection covering condition, anchorage and grounding, cleanliness, arc chute integrity, contact condition and alignment, the slow close and open check, mechanical operation, bolted-connection tightness, cell fit, the racking mechanism, puffer operation, lubrication, contact timing, motion analysis, coil current signature analysis, and a thermographic survey. The electrical work covers insulation resistance with the poles closed and again across each open pole, contact or pole resistance, optional control-wiring insulation resistance, functional tests with the breaker in the test position, trip and close coil minimum pickup voltage, optional power-factor and bushing tests, a dielectric withstand test, blowout coil circuit resistance, and heater operation. NETA ATS-2025 section 7.6.1.3 lists this as the standard acceptance sequence for these breakers.

Why it is performed

A circuit breaker spends its service life doing nothing and is judged entirely on the one operation it has to get right. Almost everything in this sequence exists to predict that operation. Contact resistance and the contact-condition inspection say whether the breaker can carry load without overheating; insulation resistance and the dielectric withstand test say whether the open gap and the solid insulation can hold off system voltage; minimum pickup voltage on the trip and close coils says whether the breaker will still operate on a depressed station battery, which is exactly the condition a fault creates; and contact timing, motion analysis, and coil current signature analysis characterize the mechanism's speed and health, since a breaker that opens late lets the fault run beyond the coordination the study assumed. The functional tests close the loop by proving each protective relay actually trips this breaker rather than only asserting an output.

When it is performed

Acceptance: after installation and before the breaker is placed in service, as part of the standard acceptance sequence, with the functional tests run in the test position before the breaker is racked in. The same form carries a maintenance service type, since the resistance measurements, timing, coil tests, and the mechanical inspection are repeated on a periodic basis and after a known fault interruption, which is what the as-found operation counter reading establishes. Insulation resistance is taken before the dielectric withstand test so the higher voltage is never applied to a pole already reading low.

How it is typically performed

With the breaker removed to the test position or de-energized, isolated, and grounded per site safety procedures, the identification data and the as-found counter reading are recorded and the inspection is worked through: arc chutes, moving and stationary contacts, the slow close and open check for binding, friction, alignment, penetration, and contact sequence, the mechanism's own mechanical operation tests, cell fit and element alignment, the racking mechanism, puffer operation, and lubrication of the moving current-carrying parts and sliding surfaces. Accessible bolted connections are verified with a calibrated torque wrench, and contact timing, mechanism motion analysis, and trip and close coil current signature analysis are recorded with the appropriate instruments. Insulation resistance is then measured for one minute at the test voltage the standard assigns to the breaker's class, from each pole to ground and between phases with the breaker closed, then across every pole with the breaker open, each reading corrected to a common temperature. Contact or pole resistance is measured and compared between poles with a low-resistance ohmmeter, and control-wiring insulation resistance is measured where the circuit can tolerate it. With the breaker in the test position it is tripped and closed from the control switch, tripped from each of its protective relays, and its mechanism charge, trip-free, and antipump functions are verified. Minimum pickup voltage is established for the trip coil and the close coil by raising the applied control voltage until the coil operates. Where they are in scope, power-factor or dissipation-factor readings are taken open and closed and the bushings are tested at their power-factor taps or by hot collar. A dielectric withstand voltage is applied to each phase with the poles not under test grounded, the blowout coil circuit resistance is measured, heaters are verified, and the as-left counter reading is taken.

What gets recorded

The breaker identification (manufacturer, model and catalog number, serial number, rated voltage, rated continuous current, interrupting rating, basic impulse level, rated control voltage, mechanism type, and equipment designation); the as-found and as-left operation counter readings; the result of each visual and mechanical item, including the slow close and open check, contact timing, motion analysis, coil current signature analysis, and the thermographic survey; the insulation-resistance test voltage and the closed pole-to-ground, phase-to-phase, and across-open-pole readings, as measured and temperature corrected; contact or pole resistance per pole; the control-wiring test voltage and reading; the functional test results; the trip and close coil minimum pickup voltages; power-factor readings open and closed and the bushing power factor, capacitance, or hot-collar results where taken; the dielectric withstand test type, applied voltage, and per-phase result; the blowout coil circuit resistance; the heater result; and the ambient temperature, relative humidity, test equipment with calibration due date, comments, and deficiencies.

How results are evaluated

Insulation resistance must meet the manufacturer's published data or, where none exists, the minimum for the breaker's nominal voltage rating in the standard's insulation-resistance table, with lower values investigated. Contact or pole resistance must not exceed the high end of the manufacturer's normal range, and without manufacturer data a pole that deviates well above the lowest of the adjacent poles or of similar breakers is investigated. Control-wiring insulation resistance has a published floor of its own, and where solid-state components in the circuit would not survive the test voltage, the manufacturer's own recommendation replaces it. The charging, closing, opening, tripping, trip-free, and antipump functions must each behave as the design intends, and each protective device must trip the breaker per the system design. Trip and close coil minimum pickup voltage follows the manufacturer's published data, with the standard's coil-pickup table used in its absence. Power-factor and dissipation-factor values are comparative: they are judged against previous results, similar breakers, or the manufacturer's data, while bushing power factor and capacitance are expected within a published percentage of the nameplate rating and hot-collar results are compared on milliampere and milliwatt loss between similar bushings. The dielectric withstand test passes when the breaker holds the applied voltage for its full duration with no sign of breakdown or insulation distress, at a voltage from the manufacturer's data or the standard's field-test table. The blowout coil circuit must show continuity, heaters must be operational, the counter must step up by exactly one count per close and open cycle, and contact timing, travel and velocity, and coil current values follow the manufacturer's published data. See the purchased NETA standard for every table value.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Entigy Solutions are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.