UltraDb
Log in Get started
<- Reference

Regulating Apparatus

Load Tap-Changer Acceptance Test

What it is

A load tap-changer acceptance test is a field protocol that proves a tap-changing transformer can change taps under load without interrupting current, and that its insulation and liquid are sound. It records the identification (manufacturer, model and catalog number, serial number, tap-changer type, kVA rating, winding voltages, phase, winding connection, impedance, liquid type, number of taps, and equipment designation) with the as-found and as-left operation counter readings. The inspection covers nameplate data against the drawings, condition, anchorage, alignment and grounding, the impact recorder, removal of shipping bracing and vent plugs, cleanliness, bolted-connection tightness, auxiliary devices, the motor, drive train, and automatic cutoff at the extreme positions, liquid level in all tanks, the manufacturer's own inspections and mechanical tests, lubrication, and a thermographic survey. The electrical work covers insulation resistance and insulation power factor taken off the neutral position under the liquid-filled transformer section, winding resistance at each tap, dynamic winding resistance, optional leakage reactance, turns ratio at all taps, an insulating-liquid screen and dissolved gas analysis, the vacuum-interrupter checks where the design uses them, an optional excitation test, and heater operation. NETA ATS-2025 section 7.12.3 lists this as the standard acceptance sequence.

Why it is performed

A load tap-changer is the only part of a transformer designed to make and break current in normal service, thousands of times, inside the same tank as the windings it regulates. That is why its acceptance test looks like a transformer test with a mechanism test wrapped around it. The mechanism side asks whether the motor, drive train, and cutoffs will stop at the end positions instead of driving through them, and whether the changer moves cleanly through every position; dynamic winding resistance is the measurement that reveals a transition contact that opens momentarily, which a static reading cannot see. The insulation side asks the ordinary transformer questions, but the readings are deliberately taken off the neutral tap so the tap winding itself is in the circuit. And the liquid carries the history of every switching operation: a tap-changer compartment accumulates arc products faster than the main tank, so the liquid screen and the dissolved gas analysis are how the switching duty is read.

When it is performed

Acceptance: after installation and before the regulating transformer is placed in service, as part of the standard acceptance sequence, with the liquid samples drawn early enough for the laboratory results to arrive with the record. The same form carries a maintenance service type, and a tap-changer is a strong candidate for interval-based and operation-count-based maintenance, since its contacts wear per operation rather than per year; the as-found counter reading is what makes that judgment possible. Turns ratio and winding resistance are re-measured after any contact replacement, and the dissolved gas analysis is repeated on the owner's interval because it trends rather than passing or failing a single time.

How it is typically performed

With the transformer de-energized, isolated, and grounded per site safety procedures, the identification data and the as-found counter reading are recorded and the inspection is worked through, including the impact recorder, the removal of shipping bracing and vent plugs, liquid levels in all tanks, the auxiliary devices, and the motor, drive train, and automatic cutoff exercised to the maximum raise and lower positions. Accessible bolted connections are verified with a calibrated torque wrench. The tap-changer is then placed on an off-neutral tap and insulation resistance is measured high-voltage to ground, low-voltage to ground, and high- to low-voltage, corrected to a common temperature, followed by insulation power factor on the same three windings, both under the procedure the liquid-filled transformer section gives. Winding resistance is measured at each tap position per phase, and dynamic winding resistance is measured through the tap-change operation so the transition behavior can be compared with the factory result. Leakage reactance is measured where it is in scope, as a three-phase equivalent and per phase. Turns ratio is measured at all tap positions and compared with the calculated ratio. An insulating-liquid sample is drawn by the standard sampling practice and tested for dielectric breakdown at the specified electrode gap, color, and visual condition, and a second sample goes to the laboratory for dissolved gas analysis. On designs with vacuum interrupters the interrupter pressures are measured and a dielectric withstand is applied across the open contacts of each bottle. An excitation test at all taps and neutral and a heater check close out the sequence.

What gets recorded

The identification (manufacturer, model and catalog number, serial number, tap-changer type, kVA rating, winding voltages, phase, winding connection, impedance, liquid type, number of tap positions, and equipment designation); the as-found and as-left counter readings; the result of each visual and mechanical item, including liquid levels and thermography; the off-neutral tap tested, the test voltage, and the insulation readings as measured and corrected; the power-factor test voltage and the three winding results; winding resistance by tap position with the maximum deviation from the adjacent windings; the special tests and adjustments performed; the dynamic winding resistance compared with the factory tests; the nameplate impedance, three-phase equivalent, per-phase leakage reactance, and the deviations; the calculated ratio, the measured ratio by tap position, and the maximum deviation; the liquid sample date with the dielectric breakdown voltage, electrode gap, color, and visual condition; the dissolved gas analysis date, laboratory, report number, standard, and results; the interrupter pressures and the vacuum bottle results; the excitation current by tap position; the heater result; and the ambient temperature, relative humidity, test equipment with calibration due date, comments, and deficiencies.

How results are evaluated

Insulation resistance must meet the manufacturer's published data or, in its absence, the standard's instrument and coil-rating table, with lower readings investigated. Winding power factor must not exceed the transformer manufacturer's published maximum or, failing that, the maximum in the standard's power-factor table for the liquid in use, and distribution units are compared with their own previous results. Winding resistance readings that vary from the adjacent-winding measurements beyond the published margin call for consulting the manufacturer, and dynamic winding resistance is compared with the factory test results. Leakage reactance is judged by deviation: the three-phase equivalent against the nameplate impedance and each phase against the average of the three, both within the published percentages. Turns-ratio results must keep a normal progression between voltage steps and stay within the published fraction of a percent of the calculated ratio. Insulating-liquid results are judged against the standard's liquid table for the liquid type and voltage class, which sets a minimum dielectric breakdown at each electrode gap, a maximum color, and a bright and clear visual requirement; dissolved gas analysis is evaluated against the transformer gas-in-oil guide rather than a NETA table. Interrupter pressure has a published ceiling and a published spread between adjacent poles when the manufacturer publishes no value, and the vacuum bottle withstand passes only if no distress appears through the full voltage-application time. Excitation results are judged by pattern for the core configuration, auxiliary devices and the motor cutoffs must operate per the design intent, liquid levels must be within the indicated tolerances, heaters must be operational, and the counter must show a change consistent with the operations performed. See the purchased NETA standard for every table value.

Governing standards

ANSI/NETA ATS-2025

ANSI/NETA ATS-2025

Purchase this standard ↗

Run this test in UltraDb.

Start free ->

UltraDb references ASTM, ANSI, IEEE, and NETA standards descriptively, to identify the published methods its forms are built from. UltraDb and Entigy Solutions are not affiliated with, endorsed by, certified by, or licensed by NETA, ASTM, ANSI, IEEE, or Megger. Standard names and section numbers are the property of their respective organizations. Always test to the edition your contract specifies.